Wire Ampacity Chart (NEC Table 310.16)

Ampacity is the maximum continuous current a conductor can carry without exceeding its temperature rating. These values are from NEC Table 310.16 for conductors in raceway, cable, or direct burial, with up to 3 current-carrying conductors, at 30°C (86°F) ambient. Derate for higher ambient temperatures or more conductors in conduit.

Ampacity Table

GaugeCu 60°CCu 75°CCu 90°CAl 75°CAl 90°C
14 AWG152025--
12 AWG2025302530
10 AWG3035403035
8 AWG4050554045
6 AWG5565755060
4 AWG7085956575
3 AWG851001107585
2 AWG9511513090100
1 AWG110130150100115
1/0 AWG125150170120135
2/0 AWG145175195135150
3/0 AWG165200225155175
4/0 AWG195230260180205
250 kcmil215255290205230
300 kcmil240285320230255
350 kcmil260310350250280
400 kcmil280335380270305
500 kcmil320380430310350

Approximate values from NEC Table 310.16. Always verify with the current NEC edition.

Ambient Temperature Correction Factors (NEC Table 310.15(B))

Multiply the table ampacity by the correction factor for your actual ambient temperature.

Ambient Temp (°C)Ambient Temp (°F)60°C Factor75°C Factor90°C Factor
10°C50°F1.291.201.15
15°C59°F1.221.151.12
20°C68°F1.151.111.08
25°C77°F1.081.051.04
30°C86°F1.001.001.00
35°C95°F0.910.940.96
40°C104°F0.820.880.91
45°C113°F0.710.820.87
50°C122°F0.580.750.82
55°C131°F0.410.670.76
60°C140°FN/A0.580.71

30°C row (highlighted) is the base case (factor = 1.00). Approx. from NEC Table 310.15(B).

Conduit Fill Derating (NEC Table 310.15(C)(1))

When 4 or more current-carrying conductors share a raceway, cable, or are bundled together, multiply the ampacity by the factor below.

Number of Current-Carrying ConductorsAmpacity Adjustment Factor
4-6 conductors80%
7-9 conductors70%
10-20 conductors50%
21-30 conductors45%
31-40 conductors40%
41+ conductors35%

Neutral conductors carrying only unbalanced load are not counted. Equipment grounding conductors are never counted. Source: NEC Table 310.15(C)(1), approx.