Conduit Fill Chart

NEC Chapter 9, Table 1 limits how much of a conduit's internal area can be filled with conductors: 53% for 1 conductor, 31% for 2, and 40% for 3 or more. The tables below show conduit internal areas and conductor cross-sectional areas to help you check fill manually or understand calculator results.

NEC Fill Limits

Number of ConductorsMax Fill %Notes
153%Single conductor (e.g., service entrance cable)
231%2-wire circuit
3 or more40%Most branch circuits and feeders

Conduit Internal Areas (NEC Chapter 9, Table 4)

Trade SizeEMT (sq in)40% Fill (sq in)PVC Sch40 (sq in)40% Fill (sq in)RMC (sq in)40% Fill (sq in)
1/2"0.3040.1220.2850.1140.3140.126
3/4"0.5330.2130.5080.2030.5490.220
1"0.8640.3460.8320.3330.8870.355
1-1/4"1.4960.5981.4530.5811.5260.610
1-1/2"2.0360.8141.9860.7942.0710.828
2"3.3561.3423.2911.3163.4081.363
2-1/2"5.8582.3434.6951.8784.8661.946
3"8.8463.5387.2682.9077.4993.000
4"14.7535.90112.5545.02212.8825.153

Approximate values from NEC Chapter 9, Table 4. Verify with current NEC edition.

THHN/THWN-2 Conductor Areas (NEC Chapter 9, Table 5)

ConductorArea (sq in)
14 AWG THHN0.0097
12 AWG THHN0.0133
10 AWG THHN0.0211
8 AWG THHN0.0366
6 AWG THHN0.0507
4 AWG THHN0.0824
3 AWG THHN0.0973
2 AWG THHN0.1158
1 AWG THHN0.1562
1/0 AWG THHN0.1855
2/0 AWG THHN0.2223
3/0 AWG THHN0.2660
4/0 AWG THHN0.3237
250 kcmil THHN0.3970
350 kcmil THHN0.5281
500 kcmil THHN0.7073

Approximate values for THHN/THWN-2 from NEC Chapter 9, Table 5. Other insulation types (XHHW, RHH, etc.) have different areas.