What Gauge Wire for 20 Amps?
Quick Reference: 20A Circuit
| Wire Gauge (Copper) | Ampacity at 75°C | Notes |
|---|---|---|
| 12 AWG | 25A | 12 AWG copper is rated 25A at 75°C. Required for 20A circuits per NEC. |
Values from NEC Table 310.16, copper, 75°C, up to 3 conductors in raceway, 30°C ambient. Derating applies for higher temperatures or more conductors in conduit.
Why "What Wire for 20 Amps?" Has More Than One Answer
- Insulation temperature rating: 60°C, 75°C, and 90°C insulation have different ampacity columns in NEC Table 310.16. Most devices terminate at 75°C, so that column is typically the right one.
- Ambient temperature: Higher ambient means the wire cannot shed heat as well. NEC Table 310.15(B) has correction factors.
- Conduit fill and bundling: More than 3 current-carrying conductors in a raceway requires derating per NEC Table 310.15(C)(1).
- Copper vs. aluminum: Aluminum has higher resistance, so you need a larger gauge to match copper ampacity.
- Voltage drop: On runs longer than 50 to 100 feet, voltage drop often drives wire sizing above what ampacity alone would require.
Ampacity Table Reference (Copper, 75°C, Up to 3 Conductors)
| Gauge | Ampacity | Gauge | Ampacity |
|---|---|---|---|
| 14 AWG | 20A | 1/0 AWG | 150A |
| 12 AWG | 25A | 2/0 AWG | 175A |
| 10 AWG | 35A | 3/0 AWG | 200A |
| 8 AWG | 50A | 4/0 AWG | 230A |
| 6 AWG | 65A | 250 kcmil | 255A |
| 4 AWG | 85A | 300 kcmil | 285A |
| 3 AWG | 100A | 350 kcmil | 310A |
| 2 AWG | 115A | 400 kcmil | 335A |
| 1 AWG | 130A | 500 kcmil | 380A |
Approximate values from NEC Table 310.16. Verify with the current edition of the NEC.
Calculate Your Wire Size
Enter your load, voltage, run length, and the calculator finds the minimum gauge that meets both ampacity and voltage drop limits:
Common Questions
Where do I find official wire ampacity tables?
NEC Table 310.16 covers conductors in conduit or cable with up to 3 current-carrying conductors. Other tables apply for direct burial, free air, and other conditions. Your electrical inspector or AHJ may require a different table depending on the installation type.
Can I just use a wire gauge chart I found online?
Many online charts skip correction factors for temperature and conduit fill. Cross-check with the actual NEC table and get a licensed electrician to review any permanent installation.
What is the difference between ampacity and voltage drop sizing?
Ampacity is about not overheating the wire. Voltage drop is about the load still seeing enough voltage. On long runs you often need bigger wire to control drop than you would for ampacity alone.
What if I need to put multiple wires in a conduit?
You will need to derate the ampacity. NEC Table 310.15(C)(1) lists adjustment factors: for 4-6 conductors, multiply by 0.8; for 7-9, by 0.7; and so on. Use our conduit fill calculator to check whether the conduit is large enough first.